Description:
Conductor - Compacted aluminium(Class 2)
Semiconductor layer - Cross linkable semiconductive polyethylene
Insulation - Cross linkable polyethylene
Max. operating temperature:
+90 °C
Flame propagation test on single cable:
-IEC 60332-1
Test voltage:
42 kV
| Nominal Cross Section mm² |
Outer diameter (mm) |
Net Weight kg/km | Conductor DC Resistance at(20°C) max. ohm/km |
Operating capacity (uF/km)) |
Delivery Length (m |
|---|---|---|---|---|---|
| 1x35/16 | 25,30 | 690 | 0,868 | 0,149 | 1000 |
| 1x50/16 | 26,50 | 755 | 0,641 | 0,164 | 1000 |
| 1x70/16 | 28,50 | 880 | 0,443 | 0,183 | 1000 |
| 1x95/16 | 30,10 | 994 | 0,320 | 0,203 | 1000 |
| 1x120/16 | 31,60 | 1 109 | 0,253 | 0,219 | 1000 |
| 1x150/25 | 33,10 | 1 307 | 0,206 | 0,237 | 1000 |
| 1x185/25 | 35,00 | 1 474 | 0,164 | 0,256 | 1000 |
| 1x240/25 | 37,30 | 1 684 | 0,125 | 0,284 | 1000 |
| 1x300/25 | 39,60 | 1 925 | 0,100 | 0,312 | 1000 |
| 1x400/35 | 43,20 | 2 366 | 0,0788 | 0,341 | 1000 |
| 1x500/35 | 46,40 | 2 765 | 0,0605 | 0,377 | 1000 |
| 1x630/35 | 52,80 | 3 279 | 0,0469 | 0,420 | 1000 |